TROUBLESHOOTING
VCC-X Operator Interface SD
82
Analog Output 4 Screen
Exhaust Fan Signal
Override Volts: -1.0
[-1.0 = Auto]
The default setting for normal operation is -1.0 volts. Voltages
between 0 to 10.0 are valid entries.
Press <ENTER> after making
a setting change and then
press <> and the next Analog Output
Override Screen
will be displayed.
Analog Output 5 Screen
Modulating Cool
Override %...: -10%
[-10 = Auto]
The default setting for normal operation is -10%. Percentages
between 0 to 100 are valid entries. Press <ENTER> after making
a setting change and then
press <> and the next Analog Output
Override Screen
will be displayed.
VCC-X Outputs Force
Analog Output 6 Screen
Mod Condenser
Override Volts: -1.0
[-1.0 = Auto]
The default setting for normal operation is -1.0 volts. Voltages
between 0 to 10.0 are valid entries.
Press <ENTER> after making
a setting change.