Orion-system VCC-X Controller Manual do Utilizador Página 53

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 52
VCC-X Operator Interface SD
VCC-X SETPOINTS
53
Setpoint Screen #49 - OAT Sensor Calibration
- Current and Offset
VCC-X Spts ID:#
OAT Sensor Cal
Current: 0.0ºF
Offset.: 0.0ºF
If the Outdoor Air Temperature Sensor is reading incorrectly, you
can use this option to enter an offset temperature to adjust the
Sensors Temperature. Line 3 will display the current Outdoor Air
Temperature Sensor Reading. Enter a positive Sensor Calibration
value in Line 4 to raise the Outdoor Air Temperature Sensor reading
or a negative value in Line 4 to lower the Sensor reading.
Description Minimum Default Maximum
OAT Sensor Calibration
Offset
-100.0ºF
(-55.5ºC)
0.0ºF
(0ºC)
100.0ºF
(55.5ºC)
Setpoint Screen #50 - CO
2
Sensor Calibration
- Current and Offset
VCC-X Spts ID:#
CO2 Sensor Cal
Current: 0ppm
Offset.: 0ppm
If the CO
2
Sensor is reading incorrectly, you can use this option
to enter an offset reading to adjust the Sensor’s Sensitivity. Line 3
will display the current CO
2
Sensor reading. Enter a positive Sensor
Calibration value in Line 4 to increase the CO
2
Sensor reading or a
negative value in Line 4 to lower the Sensor reading.
Description Minimum Default Maximum
Sensor Calibration CO
2
-500.0 PPM 0.0 PPM 500.0 PPM
VCC-X Setpoint Screens
Vista de página 52
1 2 ... 48 49 50 51 52 53 54 55 56 57 58 ... 95 96

Comentários a estes Manuais

Sem comentários