RSMV CONFIGURATION
VCC-X Operator Interface SD
66
RSMV Con guration Screens
SETUP RSM STAGING
COMPRESSOR SETTINGS
RSMV Compressor Settings Screens
From the screen below, selectCompressor Settings” and press
<ENTER>.
Setpoint Screen #1 - RSM #1 OAT Lockout
RSM 1 OAT LOCKOUT
Comp A1: 50ºF
Comp A2: 50ºF
The RSM will Lockout Compressor (Mechanical) Cooling when the
Outdoor Air Temperature is below this Compressor Cool Lockout
Setpoint.
Description Minimum Default Maximum
OAT Lockout
Compressor Cooling
-30ºF
(-34.4
ºC)
50ºF
(10ºC)
100ºF
(37.7ºC)
The RSM will Lockout Compressor (Mechanical) Cooling when the
Outdoor Air Temperature is below this Compressor Cool Lockout
Setpoint.
Description Minimum Default Maximum
OAT Lockout
Compressor Cooling
-30ºF
(-34.4ºC)
50ºF
(10ºC)
100ºF
(37.7ºC)
RSM 2 OAT LOCKOUT
Comp B1: 50ºF
Comp B2: 50ºF
Setpoint Screen #2 - RSM #2 OAT Lockout
The RSM will Lockout Compressor (Mechanical) Cooling when the
Outdoor Air Temperature is below this Compressor Cool Lockout
Setpoint.
Description Minimum Default Maximum
OAT Lockout
Compressor Cooling
-30ºF
(-34.4ºC)
50ºF
(10ºC)
100ºF
(37.7ºC)
RSM 3 OAT LOCKOUT
Comp C1: 50ºF
Comp C2: 50ºF
Setpoint Screen #3 - RSM #3 OAT Lockout
The RSM will Lockout Compressor (Mechanical) Cooling when the
Outdoor Air Temperature is below this Compressor Cool Lockout
Setpoint.
Description Minimum Default Maximum
OAT Lockout
Compressor Cooling
-30ºF
(-34.4ºC)
50ºF
(10ºC)
100ºF
(37.7ºC)
RSM 4 OAT LOCKOUT
Comp D1: 50ºF
Comp D2: 50ºF
Setpoint Screen #4 - RSM #4 OAT Lockout
Setpoint Screen #5 - Mod Cool Reset Position
& Deadband
MOD COOLING RESET
Position: 30%
Deadband: 5.0ºF
If the VFD compressor in a tandem circuit has reached 100% for the
Stage Up Delay period and the next compressor is staged on, this
screen allows you to con gure the position (capacity) that the VFD
compressor(s) will initially start at once the next compressor stages
on. If the Supply Air Temperature is above the Cooling Supply Air
Setpoint plus the Mod Cool Deadband (con gured in this screen)
when the xed compressor stages on, the VFD compressor will start
at 100% and modulate down as needed to maintain the Cooling Sup-
ply Air Setpoint. If the Supply Air Temperature is above the Cooling
Supply Air Temperature by less than this deadband amount, then
the VFD compressor will go to the Mod Cool Position (con gured
in this screen) and modulate from there as needed to maintain the
Cooling Supply Air Setpoint.
Description Minimum Default Maximum
Mod Cool Position 0% 30% 100%
Mod Cool Deadband 0.0ºF
(-17.7
ºC)
5.0ºF
(1.00ºC)
30.0ºF
(-1.11ºC)