VCC-X Operator Interface SD
VCC-X SETPOINTS
51
VCC-X Setpoint Screens
Setpoint Screen #40 - Return Air Bypass
Damper Factor Setpoint
VCC-X Spts ID:#
Return Air Bypass
Damper Factor
Setpoint: 40%
This setpoint is used when you have an EM1 Expansion Module
installed and confi gured for Return Air Bypass Damper control. The
Return Air Bypass Damper Factor Setpoint is a percentage value
that is used to calculate the Return Air Damper position in relation
to the Return Air Bypass Damper position. This provides a method
for adjusting the airfl ow through the Return Air Bypass Damper.
Increasing this percentage increases the airfl ow through the Return
Air Bypass Damper by causing the Return Air Damper to move fur-
ther towards its closed position in relation to the Return Air Bypass
Damper moving towards its open position.
Description Minimum Default Maximum
Damper Factor 0% 40% 100%
Setpoint Screen #41 - Warm-Up Supply Air
Temperature Setpoint
VCC-X Spts ID:#
Warmup Supply Air
Setpoint: 100.0ºF
Heating will be controlled to this Supply Air Setpoint during Morn-
ing Warm-Up.
Description Minimum Default Maximum
Warm-Up SAT Setpoint 40ºF
(4.44
ºC)
100ºF
(37.78ºC)
240ºF
(115.56ºC)
Setpoint Screen #42 - Cool-Down Supply Air
Temperature Setpoint
VCC-X Spts ID:#
Cooldown Supply Air
Setpoint: 55.0ºF
Cooling will be controlled to this Supply Air Setpoint during Cool-
Down.
Description Minimum Default Maximum
Cool-Down SAT Setpoint 30ºF
(-1.11
ºC)
55ºF
(12.78ºC)
80ºF
(26.67ºC)
Setpoint Screen #43 - PREHEAT-X Cool Mode
and Heat Mode Setpoints
VCC-X Spts ID:#
Preheat-X Spts
Cool Mode: 40.0ºF
Heat Mode: 60.0ºF
If using the Preheat-X Controller with the VCC-X, this screen al-
lows you to set the Preheat setpoint you want to control to during
the Cooling and the Heating Modes.
Description Minimum Default Maximum
Preheat-X Cool Mode
Setpoint
35.0ºF
(1.66ºC)
40.0ºF
(4.5ºC)
90.0ºF
(32.2ºC)
Preheat-X Heat Mode
Setpoint
35.0ºF
(1.66
ºC)
60.0ºF
(15.5ºC)
90.0ºF
(32.2ºC)
Setpoint Screen #44 - PREHEAT-X Vent Mode
Setpoint
VCC-X Spts ID:#
Preheat-X Spts
Vent Mode: 50.0ºF
If using the Preheat-X Controller with the VCC-X, this screen al-
lows you to set the Preheat setpoint you want to control to during
the Vent Mode.
Description Minimum Default Maximum
Preheat-X Vent Mode
Setpoint
35.0ºF
(1.66
ºC)
50.0ºF
(10.0ºC)
90.0ºF
(32.2ºC)
Setpoint Screen #45 - Superheat Setpoint
VCC-X Spts ID:#
Superheat
Setpoint: 15ºF
The Superheat Setpoint is the target Superheat used by the Refriger-
ant Module to correctly drive the EXV valves.
Description Minimum Default Maximum
Superheat Setpoint 1ºF
(-17.2ºC)
15ºF
(-16.9ºC)
30ºF
(-1.11ºC)