Orion-system VCM-X E-BUS Component Manual do Utilizador Página 80

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 128
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 79
VCM-X Component & Systems Wiring80
Communication Devices
FILENAME
DATE:
S. Olson
DESCRIPTION:
PAGE
BY:
Wiring & Connection Diagram
JOB NAME
1 of 1
Optional USB-Link 2 Connection Diagram
O-VCMX-JS-USBLINK2-1A.CDR
VCM-X Job Site USB-Link 2
01/04/13
Adapter
Supplied With USB-Link
PL101904
Adapter
Supplied With USB-Link
PL101905
Mini-DIN Cable
Mini-DIN Cable
Use The Adapter To Plug In To A Terminal Socket And Connect
The USB-Link On Boards That Don’t Have A Female Mini-DIN Plug Connection.
This Only Allows Communications With The Board It Is Connected To
PL101904
NOTE: .
Use The Adapter And Wire To A Terminal Block
To Connect The USB-Link To The Local Communications Loop
All Controllers
That Are Connected To The System
P 101905L
On Boards That Don’t Have A Female Mini-DIN Plug Connection.
This Allows Communications With
. See Note 1.
NOTE:
USB-Link 2
Controller With
Mini-DIN Plug
USB Cable
Supplied With
USB-Link
Connect Type A Cable End To
USB Port On Desktop Or Laptop
Personal Computer.
USB Drivers Supplied With The USB-
Link 2 Must Be Installed On Your Computer
Before USB-Link 2 Can Be Used.
NOTE:
Connect Type B Cable End To
USB Port On USB Link.
Connect Mini-DIN Cable End To
Mini-DIN Port On USB-Link.
Communication Switch
Must Be Set To Stand Alone
Or Network Depending On
Your Installation.
Mini-DIN Cable
Supplied With USB-
Link
Connect The USB-Link
Mini D Cable To The
- IN Connector On Controllers
That Are Supplied
With Them.
All
Controllers That Are
Connected To The System
- IN Female
Mini D Plug
This Allows
Communications With
.
See Note 1.
NOTE:
SHLD
SHLD
T
T
R
R
Computer
(By Others)
With Prism II
Software
Installed
Notes:
1. For Networked Systems, In The Event That You Have A CommLink II or CommLink III
And Have An EPROM Software Version Earlier Than 3.15 Installed In The CommLink,
, You Will Need An EPROM Upgrade Before You Can
View All Controllers On Your System. Contact WattMaster Technical Support For An EPROM Update.
If You Have A CommLink IV This WIll Not Be A Problem.
Even Without The EPROM Upgrade You Can Still View A Single Controller
To Do This You Must First Disconnect The Communication Loop From The Controller Your USB-Link Is
Plugged Into
Or Your MiniLink
Has An EPROM Software Version Earlier Than 3.14
Using Prism II.
. Set The USB-Link Communication Switch To Stand Alone, Set The Type Of CommLink In
Prism II To USB Link Stand Alone, And Cycle Power By Disconnecting And Reconnecting the USB Power
Supply Cable.
Line Voltage
VCM-X Unit Controller
24 VAC
(8 VA)
WARNING
OBSERVE
POLARITY
STANDALONE
NETWORK
Communication Speed Switch
Must Be Set To Low or High Speed
Depending on Your Controller’s
Baud Rate.
Figure 58: Computer Connections Using USB-Link 2
USB-Link 2 Computer Connections & Wiring
Vista de página 79
1 2 ... 75 76 77 78 79 80 81 82 83 84 85 ... 127 128