VCM-X Component & Systems Wiring
VCM-X Expansion Module Wiring
55
AO5
AO4
GND
Modular Cable
Connect To VCM-X E-BUS Controller
Modular Cable
Connect To Next Expansion
Board (When Used)
24 VAC
GND
10 VA Minimum Power
Required For
VCM-X Expansion Module
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-24VAC. Failure
to observe polarity will result in damage to one or more of the boards. Expansion Modules
must be wired in such a way that the expansion modules and the controller are always
powered together. Loss of power to the expansion module will cause the controller to become
inoperative until power is restored to the expansion module.
Return Air Bypass
Damper Actuator
(0-10 VDC)
Return Air
Damper Actuator
(0-10 VDC)
Belimo Actuator Wiring
Shown. Consult Factory
For Other Manufacturer
Wiring Instructions.
3Y1
3Y1
2 +
2 +
1 COM
1 COM
VCM-X
Expansion
Module
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RELAY 2
RELAY 1
RELAY 3
RELAY 4
RELAY
COMMON
I2C
EXPANSION
I2C
EXPANSION
AO1 = BUILDING PRESSURE CONTROL VFD OR
DAMPER ACTUATOR (0-10 OR 2-10 VDC)
= MODULATING HEATING SIGNAL
(0-10 VDC OR 2-10 VDC)
= MODULATING COOLING/DIGITAL SCROLL
SIGNAL (0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
= RETURN AIR DAMPER ACTUATOR
(0-10 VDC)
= RETURN AIR BYPASS DAMPER ACTUATOR
(0-10 VDC)
= GROUND FOR ANALOG OUTPUTS
= GROUND FOR ANALOG OUTPUTS
AO2
AO3
AO4
AO5
GND
GND
BI1 = HOOD ON - N.O. INPUT
BI2
BI3
BI4
BI5
BI6
BI7
BI8
= DIRTY FILTER - N.O. INPUT
= PROOF OF FLOW - N.O. INPUT
= REMOTE FORCED OCCUPIED - N.O. INPUT
= REMOTE FORCED HEATING - N.O. INPUT
= REMOTE FORCED COOLING - N.O. INPUT
= SMOKE DETECTOR - N.C. INPUT
= REMOTE DEHUMIDIFICATION - N.O. INPUT
ANALOG INPUT
JUMPER SETTINGS
MUST BE SET AS
SHOWN FOR
PROPER
OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE
OBSERVED OR THE BOARD
WILL BE DAMAGED
www.orioncontrols.com
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
ANALOG INPUT
JUMPER
SETTINGS
RELAY 1 = RELAY 3 =
RELAY 2 = RELAY 4 =
IT IS SUGGESTED
THAT YOU WRITE THE
DESCRIPTION OF
THE RELAY OUTPUTS
YOU ARE USING IN
THE BOXES
PROVIDED ABOVE
WITH A PERMANENT
MARKER (SHARPIE®)
WattMaster Label
#LB102034-01
NOTE:
ALL BINARY INPUTS MUST BE 24 VAC ONLY.
AI1 = OUTDOOR AIR RH SENSOR (0-5 VDC)
AI2
AI3
AI4
GND
GND
= INDOOR AIR RH SENSOR (0-5 VDC)
= CO2 (0-10 VDC)
= BUILDING STATIC PRESSURE (0-5 VDC)
= GROUND FOR ANALOG INPUTS
= GROUND FOR ANALOG INPUTS
+V
SIG
GND
PR OUT
GND
SUCTION PRESSURE
TRANSDUCER CONNECTION
FOR HVAC UNITS WITHOUT
DIGITAL COMPRESSOR
TO VCM-X INPUT
TERMINALS AI5 & GND
OE333-23-EM-A VCM-X EXPANSION MODULE
VCM
WARNING
OBSERVE
POLARITY
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RELAY 2
RELAY 1
RELAY 3
RELAY 4
RELAY
COMMON
I2C
EXPANSION
I2C
EXPANSION
AO1 = BUILDING PRESSURE CONTROL VFD OR
DAMPER ACTUATOR (0-10 OR 2-10 VDC)
= MODULATING HEATING SIGNAL
(0-10 VDC OR 2-10 VDC)
= MODULATING COOLING/DIGITAL SCROLL
SIGNAL (0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
= RETURN AIR DAMPER ACTUATOR
(0-10 VDC)
= RETURN AIR BYPASS DAMPER ACTUATOR
(0-10 VDC)
= GROUND FOR ANALOG OUTPUTS
= GROUND FOR ANALOG OUTPUTS
AO2
AO3
AO4
AO5
GND
GND
ANALOG INPUT
JUMPER SETTINGS
MUST BE SET AS
SHOWN FOR
PROPER
OPERATION
24 VAC POWER
ONLY
WARNING!
POLARITY
MUST BE
OBSERVED OR
THE BOARD
WILL BE
DAMAGED
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
ANALOG INPUT
JUMPER
SETTINGS
RELAY 1 = RELAY 3 =
RELAY 2 = RELAY 4 =
IT IS SUGGESTED
THAT YOU WRITE THE
DESCRIPTION OF
THE RELAY OUTPUTS
YOU ARE USING IN
THE BOXES
PROVIDED ABOVE
WITH A PERMANENT
MARKER (SHARPIE®)
WattMaster Label
#LB102034-01-A
Rev.: 1L
NOTE:
ALL BINARY INPUTS MUST BE 24 VAC ONLY.
+V
SIG
GND
PR OUT
GND
SUCTION PRESSURE
TRANSDUCER CONNECTION
FOR HVAC UNITS WITHOUT
DIGITAL COMPRESSOR
TO VCM-X INPUT
TERMINALS AI5 & GND
BI1 = EMERGENCY SHUTDOWN - N.C. INPUT
= DIRTY FILTER - N.O. INPUT
= PROOF OF FLOW - N.O. INPUT
= REMOTE FORCED OCCUPIED - N.O. INPUT
= REMOTE FORCED HEATING - N.O. INPUT
= REMOTE FORCED COOLING - N.O. INPUT
= HOOD ON - N.O. INPUT
= REMOTE DEHUMIDIFICATION - N.O. INPUT
BI2
BI3
BI4
BI5
BI6
BI7
BI8
www.aaon.com
www.orioncontrols.com
VCM-X Expansion Module
Orion No.:OE333-23-EM
AAON No.:
R69190
AI1 = OUTDOOR AIR RH SENSOR (0-5 VDC)
AI2
A3
AI4
GND
GND
= INDOOR AIR RH SENSOR (0-5 VDC)
= ECONOMIZER FEEDBACK
= BUILDING STATIC PRESSURE (0-5 VDC)
= GROUND FOR ANALOG INPUTS
= GROUND FOR ANALOG INPUTS
I
FILENAME
DATE:
S. Olson
DESCRIPTION:
PAGE
BY:
JOB NAME
OVCMX-RA-BYP-Wr-1B.cdr
1 of 1
05/15/15
VCM-X Expansion Module
Return Air Bypass Wiring
Return Air Bypass
Figure 36: Return Air Bypass Wiring
Vista de página 54
1 2 ... 50 51 52 53 54 55 56 57 58 59 60 ... 127 128

Comentários a estes Manuais

Sem comentários

Apple CP-X255 manuales

Manuales del propietario y guías del usuario para Proyectores Apple CP-X255.
Ofrecemos 5 manuales en pdf Apple CP-X255 para descargar gratis por tipos de documentos: Manual de usuario, Información técnica, Instrucciones de operaciones


Apple CP-X255 Manual de usuario (108 paginas)


Marca: Apple | Categoria: Projectors | Tamaño: 7.73 MB |

 

Tabla de contenidos

CP-S245/CP-X255

1

关于包装箱中的物品

3

否则会导致烫伤。

4

钟,让投影机充分冷却。仅可在这些异常情况下按下重启开关。

5

对于机型 CP-X255

8

对于机型 CP-S

8

调节投影机的脚撑

9

用 RGB IN OUT 开关按

12

钮选择 RGB IN2(如果

12

未按下该按钮,则选择

12

RGB IN2)。

12

连接 VCR/DVD 播放机的实例

13

连接到显示器 (输出)

13

连接到扬声器带放大器 (输出)

13

电源打开时,将发射强烈光线。请勿直视投影机的镜头或通风口。

17

PAGE DOWN

18

选择输入信号(续)

19

请用 USB 电缆将投影机的 USB 端子连接到计算机。

23

► 鼠标 / 键盘控制的错误操作有可能造成设备的故障。

23

RESET 按钮

24

ENTER 按钮

24

用简易菜单可以执行下表中显示的项目。

25

用投影机或遥控器上的光标按钮 ▲/▼ 选择项目。

25

接着参照下表进行操作。

25

伽马 [自定义 1]

27

用输入菜单可以执行下表中显示的项目。

32

用投影机或遥控器上的光标按钮 ▲/▼ 选择项目,然后按投

32

继续。接着参照下表进行操作。

32

用设置菜单,可以选择下表中所列的选项。

34

用屏幕菜单可以执行下表中显示的项目。

35

38

192. 168. 254

40

255. 255. 0

40

    ,  +   :否 ,   :是

41

请参阅另册网络功能的有关章节。

42

通知事项 •

44

空气过滤器(续)

46

更换内置时钟的电池

47

联系您的经销商或服务公司。

49

与经销商或服务公司联系。

50

投影机内部过热时,出于安全目的,电源自动关闭并且指示灯也

51

容易误认为是故障的现象

52

容易误认为是故障的现象(续)

53

请联系您的经销商或服务公司。他们会告诉您适用的保修条款。

55

本规格有可能因为技术改进等原因不经预告而发生变更。

55

249 mm100 mm

56

仅限于 CP-S245/X255

57

使用网络功能之前…

59

通过互联网浏览器设置和控制投影机

60

下表为管理者 ID、用户 ID 和密码的出厂缺省设定。

61

Network Information

63

Network Settings

64

Port Settings

65

Mail Settings

66

Alert Settings

67

Alert Settings(续)

68

点击 [Apply] 键保存设置。

71

Schedule Settings

72

Date/Time Settings

74

Date/Time Settings(续)

75

Security Settings

76

Projector Control

77

Projector Control(续)

78

Projector Status

79

Network Restart

80

通过电子邮件发出失败和警告报警

81

通过 SNMP 操纵投影机

83

通过程式控制投影机

84

日期 / 时间设置

85

通过网络进行命令控制

89

命令控制设置(续)

90

Initial set signals

95

Connection to the ports

96

RJ-45 jack

98

RS-232C Communication

99

Instruction Manual

108

DZ-GX3100E/DZ-BX37E/DZ-BX35E

108

DZ-GX3300E/DZ-GX3200E

108





Más productos y manuales para Proyectores Apple

Modelos Tipo de documento
LP 650 Manual de usuario   GY-HM650 New Product News (2 pg, April 2012) [en] , 2 paginas