Orion-system PT-Link-LON Manual do Utilizador Página 9

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 40
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 8
PT-Link Interface
PT-Link-LON
®
Technical Guide
9
Explicit Addressing & Domain Table Setup
To use explicit addressing, the client needs to change the factory settings
contained in the PT-Link-LON’s con guration le (con g.csv). The
following are the steps to change the con guration le from implicit to
explicit addressing:
1.) Upload and open the con g.csv le.
2.) Locate the “Connections” section.
3.) Locate the “Lonworks_Server” column and change the
value from “Implicit” shown in Figure 13 to “Explicit”
shown in Figure 14. You should also change the “Lon
works _Input” and “Lonworks_Outputs” from Update to
Polled.
In addition, the PT-Link-LON must have its domain, subnet, and node
IDs set. This feature is enabled in the con guration le by lling out
the Title and System_Address elds of the PT-Link-LON parameters
as follows:
//==================================================
//
// Common Information
//
Bridge
System_Address ,Title
23 ,”:D48:S01:Wattmaster Explicit Lon v1.00d”
Figure 15: PT-Link-LON Domain and Subnet Setting
The Title eld must start with “:D”, followed by the domain_id in
hexadecimal notation, followed by “:S”, followed by the subnet_id in
hexadecimal notation, and enclosed by “:”. The domain length is auto-
matically determined by the number of digits in the [domain_id] eld.
With 2 hexadecimal digits constituting 1 byte, “:D123456:”, for example,
would have a length of 3.
Once the domain table has been set, the “:Dxx:Sxx:” part of the Title
eld will be removed.
Now the Title eld will be left with [Title continued…] which may be
the Node self documentation string or any title.
After the changes are done, do not forget to save the le, download
the new con guration le, and restart the PT-Link-LON. Refer to the
Download Section that follows.
Troubleshooting the PT-Link Controller
Figure 13: PT-Link-LON Implicit Con guration
Figure 14: PT-Link-LON Explicit Con guration
Vista de página 8
1 2 3 4 5 6 7 8 9 10 11 12 13 14 ... 39 40

Comentários a estes Manuais

Sem comentários