PT-Link-LON
®
Technical Guide
PT-Link Interface
30
Appendix E - SA Controller LON Parameters
SNVTs for the SA Controller
Binary Output SNVTs are SNVT_lev_disc
all other SNVTs are SNVT_count_inc_f
Parameter Name Object Description
Expansion
Relay 8
ExRly8 Binary
Output
Current status of relay 13.
Expansion
Relay 9
ExRly9 Binary
Output
Current status of relay 14.
Expansion
Relay 10
ExRly10 Binary
Output
Current status of relay 15.
Expansion
Relay 11
ExRly11 Binary
Output
Current status of relay 16.
Expansion
Relay 12
ExRly12 Binary
Output
Current status of relay 17.
Expansion
Relay 13
ExRly13 Binary
Output
Current status of relay 18.
Expansion
Relay 14
ExRly14 Binary
Output
Current status of relay 19.
Expansion
Relay 15
ExRly15 Binary
Output
Current status of relay 20.
Expansion
Relay 16
ExRly16 Binary
Output
Current status of relay 21.
Emergency
Shutdown
Alarm
EmerAlm Binary
Output
Alarm that indicates
Emergency Shutdown.
Drain Pan
Over ow
DrnAlm Binary
Output
Alarm that indicates over ow of
the drain pan.
Proof of
Water Flow
Alarm
PoWFAlm Binary
Output
Alarm that indicates no
Proof of Water Flow.
Entering Air
Temperature
Alarm
EaTpAlm Binary
Output
Alarm that indicates
failure in the Entering Air
Temperature Sensor.
SNVTs for the SA Controller
Binary Output SNVTs are SNVT_lev_disc
all other SNVTs are SNVT_count_inc_f
Parameter Name Object Description
Dirty Filter
Detected
DrtFlAlm Binary
Output
Alarm that indicates
the lters are dirty.
Control
Temperature
Cool Failure
CtrlTpCF Binary
Output
This alarm is activated if the
control temperature does not
get within 5°F to the occupied
cooling setpoint in an hour in the
cooling mode. This alarm is not
used in 100% outside air units or
supply air control.
Control
Temperature
Heat Failure
CtrlTpHF Binary
Output
This alarm is activated if the
control temperature does not
get within 5°F to the occupied
heating setpoint in an hour in the
heating mode. This alarm is not
used in 100% outside air units or
supply air control.
Space
Temperature
Sensor Lost
SpcTpAlm Binary
Output
Alarm that indicates a failure in
the space temperature sensor.
On Board
Relay 1
OnRly1 Binary
Output
Current status of relay 1.
On Board
Relay 2
OnRly2 Binary
Output
Current status of relay 2.
On Board
Relay 3
OnRly3 Binary
Output
Current status of relay 3.
On Board
Relay 4
OnRly4 Binary
Output
Current status of relay 4.
On Board
Relay 5
OnRly5 Binary
Output
Current status of relay 5.
Expansion
Relay 1
ExRly1 Binary
Output
Current status of relay 6.
Expansion
Relay 2
ExRly2 Binary
Output
Current status of relay 7.
Expansion
Relay 3
ExRly3 Binary
Output
Current status of relay 8.
Expansion
Relay 4
ExRly4 Binary
Output
Current status of relay 9.
Expansion
Relay 5
ExRly5 Binary
Output
Current status of relay 10.
Expansion
Relay 6
ExRly6 Binary
Output
Current status of relay 11.
Expansion
Relay 7
ExRly7 Binary
Output
Current status of relay 12.
SA Controller PT-Link-LON
®
Property Identi er:
The PT-Link-LON
®
Link amends the following property identity to the
BACnet
®
property identi er.
LONPropertyIdenti er :
VcmxControlStatusBits ::= ENUMERATED {
Off (0),
Vent (1),
Cool (2),
Heat (3),
Dehum (4),
Dehum Cool (5),
Dehum Heat (6),
Warm Up Mode (7)
}