PT-Link II LON
®
Technical Guide
PT-Link II Interface
52
Appendix F - SA Controller LON Parameters
SNVTs for the SA Controller
Binary Output SNVTs are SNVT_lev_disc
all other SNVTs are SNVT_count_inc_f
Parameter Name Object Description
Proof of
Water Flow
Alarm
PoWFAlm Binary
Output
Alarm that indicates no
Proof of Water Flow.
Entering Air
Temperature
Alarm
EaTpAlm Binary
Output
Alarm that indicates
failure in the Entering Air
Temperature Sensor.
SNVTs for the SA Controller
Binary Output SNVTs are SNVT_lev_disc
all other SNVTs are SNVT_count_inc_f
Parameter Name Object Description
Space
Temperature
Sensor Lost
SpcTpAlm Binary
Output
Alarm that indicates a failure in
the space temperature sensor.
On Board
Relay 1
OnRly1 Binary
Output
Current status of relay 1.
On Board
Relay 2
OnRly2 Binary
Output
Current status of relay 2.
On Board
Relay 3
OnRly3 Binary
Output
Current status of relay 3.
On Board
Relay 4
OnRly4 Binary
Output
Current status of relay 4.
On Board
Relay 5
OnRly5 Binary
Output
Current status of relay 5.
Expansion
Relay 1
ExRly1 Binary
Output
Current status of relay 6.
Expansion
Relay 2
ExRly2 Binary
Output
Current status of relay 7.
Expansion
Relay 3
ExRly3 Binary
Output
Current status of relay 8.
Expansion
Relay 4
ExRly4 Binary
Output
Current status of relay 9.
Expansion
Relay 5
ExRly5 Binary
Output
Current status of relay 10.
Expansion
Relay 6
ExRly6 Binary
Output
Current status of relay 11.
Expansion
Relay 7
ExRly7 Binary
Output
Current status of relay 12.
Expansion
Relay 8
ExRly8 Binary
Output
Current status of relay 13.
Expansion
Relay 9
ExRly9 Binary
Output
Current status of relay 14.
Expansion
Relay 10
ExRly10 Binary
Output
Current status of relay 15.
Expansion
Relay 11
ExRly11 Binary
Output
Current status of relay 16.
Expansion
Relay 12
ExRly12 Binary
Output
Current status of relay 17.
Expansion
Relay 13
ExRly13 Binary
Output
Current status of relay 18.
Expansion
Relay 14
ExRly14 Binary
Output
Current status of relay 19.
Expansion
Relay 15
ExRly15 Binary
Output
Current status of relay 20.
Expansion
Relay 16
ExRly16 Binary
Output
Current status of relay 21.
Emergency
Shutdown
Alarm
EmerAlm Binary
Output
Alarm that indicates
Emergency Shutdown.
Drain Pan
Overfl ow
DrnAlm Binary
Output
Alarm that indicates overfl ow of
the drain pan.
SA Controller PT-Link II LON
®
Property Identifi er:
The PT-Link II LON
®
Link amends the following property identity to
the LON
®
property identifi er.
LONPropertyIdentifi er :
SAUnitMode ::= ENUMERATED {
Unoccupied (0),
RemoteContactOccupied (1),
NormalScheduleOccupied (2),
PushButtonOrZoneOverride (3),
HolidayModeActive (4),
UnoccupiedZoneDemand (5),
RemoteScheduleOverride (6),
CurrentOutputForceMode (7),
SATHighOrLowCutOff (8),
CO2OverrideInProgress (9),
PurgeModeActive (10)
}
SAControlStatusBits ::= ENUMERATED {
Off (0),
Vent (1),
Cool (2),
Heat (3),
Dehum (4),
Dehum Cool (5),
Dehum Heat (6),
Warm Up Mode (7)
}
Comentários a estes Manuais