Orion-system CO2 Sensor v.1 Manual do Utilizador Página 9

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 8
Technical Guide
CO
2
SENSOR
9
Figure 6: LED ON/OFF Button and Board LEDs
Figure 7: CO
2
Sensors Front LED
TB1 Terminal Block (CO
2
Reading)
The TB1 terminal block should only be used to test the sensor when the
sensor cable is plugged into the controller and the sensor and controller
are powered up. Directions: Set the meter for DC volts and connect
the GND probe to the GND terminal and the + probe to the CO
2
0-5
terminal. Look at the output voltage and record it. Multiply the voltage
times 400. The value should match the CO
2
as read on the System Man-
ager TS, Modular System Manager, Modular Service Tool, or Prism. If
the signal doesn’t match the sensor reading, call WattMaster Controls
for a replacement.
Troubleshooting
Vista de página 8
1 2 3 4 5 6 7 8 9 10 11 12

Comentários a estes Manuais

Sem comentários