Orion-system SA Controller Manual do Utilizador Página 51

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 68
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 50
SA Controller Operator Interface
Programming
51
VAV/Zone Controller Setpoint Screens
Setpoint Screen #17 - Sensor Calibration for
Space Temp and Supply Air Temp
Sensor Calibration
SPC: XXX.Xº XXX.Xº
SAT: XXX.Xº XXX.Xº
[SAT Only if Sensor]
The Thermistor Type III sensor readings can be calibrated. Enter a
Positive value to increase a reading and a Negative value to decrease
a reading.
Note: The Supply Air Temperature calibration offset only oper-
ates on the reading when the VAV/Zone Controller has
its own Supply Air Temperature sensor installed on the
AUX2 input. If the supply temperature is received from
a global broadcast, you will need to go to the air handler
to calibrate the temperature reading.
Description Minimum Default Maximum
SPC (Space Temp) -100ºF 0ºF +100ºF
SAT (Supply Air) -100ºF 0ºF +100ºF
Vista de página 50
1 2 ... 46 47 48 49 50 51 52 53 54 55 56 ... 67 68

Comentários a estes Manuais

Sem comentários