Technical Guide
HB Mini Controller
20
Appendix
The HB Mini Controller has many setpoints that are user adjustable.
This adjustability allows the installer complete control of all major unit
operating characteristics during the setup and commissioning phase of
the HB unit installation. It also allows a service technician the ability to
change setpoints to monitor and record unit operation to determine if
the unit is functioning as specified. The tables that follow show the
available setpoints for each classification or control group provided on
the HB Mini Controller.
Cooling Control Setpoints
Description Min. Default Max.
Cooling Stages 1 2 2
Minimum Off Time 180 Sec 180 Sec 900 Sec
Minimum On Time 300 Sec 300 Sec 900 Sec
Staging Up Delay Interval 180 Sec 180 Sec 900 Sec
Staging Down Delay Interval 60 Sec 60 Sec 900 Sec
Low Pressure Delay Period 5 Sec 30 Sec 60 Sec
Low Pressure Safety 5 Sec 5 Sec 30 Sec
Low Pressure Max. Trip Point 1 3 5
Fan Off Delay Period 1 Sec 45 Sec 120 Sec
Auto Staging Up Delay 180 Sec 600 Sec 900 Sec
Table 4: Cooling Control Setpoints
Heating Control Setpoints
Description Min. Default Max.
Heating Stages 1 3 3
Minimum Off Time 60 Sec 60 Sec 900 Sec
Minimum On Time 120 Sec 120 Sec 900 Sec
Staging Up Delay Interval 180 Sec 180 Sec 900 Sec
Staging Down Delay Interval 60 Sec 60 Sec 900 Sec
Heat Safety Maximum Count 1 3 5
Fan Off Delay Period 1 Sec 120 Sec 180 Sec
Auto Stage Up Delay 180 Sec 600 Sec 900 Sec
Table 5: Heating Control Setpoints
Temperature Control Setpoints
Description Min. Default Max.
Cooling Lockout
Temperature
32° F 40° F 80° F
Heating Lockout
Temperature
40° F 80° F 120° F
Table 6: Temperature Control Setpoints
Miscellaneous Control Setpoints
Description Min. Default Max.
Force Mode Timer 1 Min 60 Min 240 Min
Table 7: Miscellaneous Control Setpoints