TROUBLESHOOTING
MODGAS-XWR Technical Guide
22
Troubleshooting Alarms
Mechanical Failure:
Check relay outputs on the MODGAS-XWR for 24
VAC output.
Verify the SAT OPTIONS jumper settings on the
MODGAS-XWR for Supply Air Temperature Sensor.
Verify gas valve LED is solid. Try forcing valves (refer
to Force Screens in this guide).
Verify that the Supply Air Temperature Sensor is
connected to SAT and GND on the MODGAS-XWR
(stand-alone mode) or to AI2 and GND on the Main
Controller (communicating mode).
Verify Supply Air Temperature Sensor probe is
mounted correctly in supply duct.
Remove SAT and GND wiring from the MODGAS-
XWR and ohm sensor out (this may indicate open or
failed wiring). Refer to chart in back of this guide for
readings.
Supply Air Temperature Failure:
Verify that the Supply Air Temperature Sensor is
connected to the SAT and GND on the MODGAS-
XWR (stand-alone mode) or to AI2 and GND on the
Main Controller (communicating mode).
Remove SAT and GND wiring from MODGAS-XWR
and ohm sensor out (this may indicate open or failed
wiring). Refer to chart in back of this guide for
readings.
Verify the SAT OPTIONS jumper settings on the
MODGAS-XWR for the Supply Air Temperature
Sensor.
SAT Cutoff Mode:
Remove SAT and GND wiring from the MODGAS-
XWR and ohm sensor out (this may indicate open or
failed wiring). Refer to chart in back of guide for
readings.
With Supply Air Sensor disconnected from the
MODGAS-XWR, set volt meter to DC volts and
measure voltage between SAT and GND on board.
Refer to chart in back of this guide for readings.
Verify Supply Air Temperature Sensor reading in duct
with 3rd party temperature testing device.
Communications Loss:
Check COMM LED on MODGAS-XWR.
Verify 24 VAC power to all interconnected WattMaster
controllers.
Verify E-BUS connection between the MODGAS-
XWR and associated WattMaster controllers.
In communication mode (connected to an AAON unit
Controller with modular cable), con rm that Main
MODGAS screens shows COMM MODE that Main
Controllers MODGAS status screen displays
MODGAS-XWR’s Position %.
Troubleshooting Alarms